Protector for indoor installation of electric line ATSOCKET 5kA
Single phase protection for indoor installation of power supply lines.
Its small size allows it to be located close to the electrical outlets that will be used by users.
Single phase protection for indoor installation of power supply lines.
Its small size allows it to be located next to the current outlets that will be used by users. It contains an effective protection for electric-pho-electrical supply lines. Fine protection according to the cascade protection recommended in the Low Voltage Regulation (REBT ITC23). Type 3 protection according to the UNE-EN 61643-11 standard and the GUBABT-23 of the REBT. Suitable for equipment of Categories I, II, III and IV according to ITC-BT-23 of the REBT.
Features
- Short response time
- They do not produce deflagration.
- They do not produce interruption of the supply lines at any time.
- Modular protection of small size.
- Thermodynamic control device and audible warning.
- Coordinated with the protectors of the ATSHOCK, ATSHIELD, ATSUB and ATCOVER series.
Installation
They are installed in parallel with the low voltage line, with connections to the phase, to the neutral and to earth.
The installation must be done without voltage on the line. It is recommended to be used in installations where equipment sensitive to transient overvoltages (computers, printers, servers, etc.) can be installed, always coordinated with protectors of type 1 or 2 in the previous panel.
The connection to earth is essential. In order for the protection to be correct, the ground connections of the entire installation must be connected directly or through sparks, and its resistance must be less than 10Ω. If the instructions in this file are not used or used, the protection guaranteed by This team can be compromised.
Specifications
Protection categories according to REBT | I, II, III y IV |
Type of tests according to UNE-EN 61643-11 | Type 2 |
Rated voltage | 230V AC |
Maximum operating voltage | 255V AC |
Nominal frecuency | 50 – 60Hz |
Rated discharge current | 5kA (wave 8 / 20μs) |
Maximum discharge current | 15kA (wave 8 / 20μs) |
Protection level for wave 8 / 20μs | 1400V |
Response time | < 10ns |
Work temperature | -40ºC to + 70ºC |
Dimensions | 40 x 40 x 10mm |
Protector status | Inside |
Connection type | Parallel (one port) |
Nº of poles | 2 |
Housing material | ABS |
Protection of the housing | IP20 |
Insulation resistance | > 1014Ω |
Self-extinguishing housing | Type V-0 according to UNE-EN 60707 (UL94) |
Connections L / N / GND | Section 2,5mm2 Length 150mm |
CE, RoHS
Summary
0