DAT CONTROLER® PLUS 60 AT-1560 Early Streamer Emission air terminal. (∆t 60µs)
DAT CONTROLER® PLUS 60: Early Streamer Emission air terminal. Advance time: 60 µs. Material: Stainless steel AISI 316L.
DAT CONTROLER® PLUS 60: Early Streamer Emission air terminal. Advance time: 60 µs. Material: Stainless steel AISI 316L.
Features
- Advance time: 60 µs obtained according to UNE21186:2011 tests.
- AENOR product certification.
- Withstand current higher than 200kA (10/350µs wave).
- Certificate of performance under rain (Insulation > 95% according to EN 60060).
- No external power supply required.
- Protection radius up to 120 meters according to NF C 17102 and UNE21186.
- Certificate of use in explosive atmospheres (ATEX).
Specifications
Reference | AT-1560 |
Length | 120 mm |
Width | 120 mm |
Height | 551 mm |
Weight | 4635 g |
Materials | AISI 316L stainless steel |
IP COde | IP67 |
Work temperature | -25°C to 88°C |
internal insulation | Polyurethane resin |
Fixing | M20 male thread |
Type of air terminal | Electropulsator (emits impulses) |
Advance time (ΔT) in certified striking | 60 µs |
Protection radius (m) | |
Height for protection radius | 2, 4, 6, 8, 10, 20, 60 |
Protection radius (m) for Level I | 31, 63, 79, 79, 79, 80, 80 |
Protection radius (m) for Level II | 35, 69, 87, 87, 88, 89, 90 |
Protection radius (m) for Level III | 39, 78, 97, 98, 99, 102, 105 |
Protection radius (m) for Level IV | 43, 85, 107, 108, 109, 113, 120 |
Tested current | 20 x 200kA + 5 x 250kA (10/350µs wave) |
Standard deviation ratio ESE/Simple rod: | <0.8 |
Standartd | Complies with NF C 17-102:2011; UNE 21186:2011; NP 4426:2013 |
Certifications and tests
- AENOR Product Certification of accordance with UNE 21186 standard
- Withstand current certificate for 20 impacts of 100 kA (10/350 µs)
- Certified advance time
- Certificate of unalterable performance under rain applying the standard EN 60060-1:2012
- Radius protection certificate and regulation compliance (UNE 21186, NFC 17-102)
- Certificate of use in explosive atmospheres (ATEX).
- Manufactured according to ISO 9001 and following ISO 14001 environmental management standard
Diagram(mm)
Installation
ESE air terminal protection radius depends on its height related to the surface to be protected, its advance time ∆T and the protection level.
The installation of DAT CONTROLER® PLUS air terminals should follow the standards NF C 17-102:2011, UNE 21186:2011 and NP 4426:2013.
The air terminal should be at least 2 meters higher than any object to be protected.
Summary
0
(0 Reviews)
Select a row below to filter reviews.
No customer reviews for the moment.