The IC-600 is an instrument designed for professional electricians and plug-in hybrid and electric vehicle charging station installers. It is valid for use in domestic and industrial electrical installations.
The team performs all the necessary tests to verify the safety of electrical installations in TT and TN systems. Measurements include continuity, insulation, RCD, loop, line, voltage, frequency, ground resistance check, and phase sequence check.
The user interface design includes a unique step-by-step guide for each test that assists the user in connecting the instrument to the setup and making measurements. The large LCD graphic display is accompanied by two red and green Pass/Fail LED indicators respectively located on either side for easy interpretation of measurement results.
Results can be quickly saved and viewed on the PC and downloaded with the included software for evaluation and professional post-test reports.
Features
- Insulation resistance with DC voltage.
- Continuity of PE conductors with test current of 200 mA and change of polarity.
- Continuity of PE conductors with 7 mA test current (continuous measurement) without RCD tripping.
- Line impedance and loop impedance.
- Loop impedance with RCD trip blocking function.
- TRMS (True RMS) voltage and frequency.
- phase sequence.
- RCD test (general and selective, type AC, A and B).
- Earth resistance (3-wire method).
Specifications
insulation resistance |
Up to 250 VDC: 0 to 199.9 MΩ Up to 1 kVDC: 0 to 1 MΩ |
|
200 mA continuity of PE conductor |
0 to 1999 MΩ |
|
low resistance continuity measurement |
7 mA test current 0 to 1999 MΩ |
|
Loop impedance (EN 61557-3) |
0 to 9.99kΩ |
|
Line impedance (EN 61557-3) |
0 to 9.99kΩ |
|
|
|
|
Phase sequence (EN 61557-7) |
1-2-3 or 3-2-1 |
|
RCD check (EN 61557-6) |
10mA to 1A |
|
touch voltage UC |
0 to 99.9V |
|
Shooting time |
From 0 ms to max time |
|
trip current |
- 0.2 x IΔN to 1.1 x IΔN (AC type)
- 0.2 x IΔN to 2.2 x IΔN (type A, IΔN < 30 mA)
- 0.2 x IΔN to 1.5 x IΔN (type A, IΔN ≥ 30 mA)
- 0.2 x IΔN to 2.2 x IΔN (type B)
|
|
Earth resistance (EN 61557-5) |
0 Ω to 9999 Ω |
|
APPLICABLE REGULATIONS |
functionality
Electromagnetic compatibility
- IEC/EN 61326-1
- IEC/EN 61326-2-2
Security
- IEC/EN 61010-1
- IEC/EN 61010-031
Other reference standards for tests:
- VDE 0413
- IEC/EN 61008
- IEC/EN 61009
- IEC/EN/HD 60364
- HD 384
- BS 7671
- IEC/TR 60755
- IEC 64.8
- AS/NZ-3760
- AS/NZ 3018
|
|
Downloads
INSTRUCTION MANUAL (SPANISH)
Product sheet (Spanish)